Full Line Product Catalog

TTX-2 & TTX-5 Addressable Transducers

TTX-2 & TTX-5 SPECIFICATIONS Number of Logic Units per loop 1-127* Accuracy

± 0.25 PSI @20° C

Operating temperature Weigh (single pressure transducer mounted) Overall dimensions

-40° F to +130° F (-40° C to +54° C)

6.25 lbs (2.83kg)

7.5" W x 2.75" D x 6.3" H (19.1 cm x 7 cm x 16 cm)

Electrical

(supplied by host monitoring system)

Operating voltage 16 to 56 VDC Standby current per unit 60-120 µA Signaling current per unit 1.3-1.7 mA

Tolerable unbalanced induced current (AC noise) Mechanical Operating pressure Overpressure capacity

1.0A (peak to peak)

0.0-9.5 PSIG (0-0.67 kg/cm)

45 PSIG (3.16 kg/cm)

Operational life

Greater than 250,000 cycles

Body and manifold construction

Tin plated brass or bronze

Ambient pressure range 0-10,000 feet (0-3048m) elevation (field adjustable)

*Subject to limitations imposed by Loop Resistance and Placement of Logic Units along the pair.

Made with FlippingBook flipbook maker